Grains per pound: GPP, dew point, depression
Grains per pound (GPP) is the weight of water vapor in one pound of dry air (7,000 grains = 1 lb). Unlike relative humidity it does not change with temperature alone, so it shows whether water is actually being removed. Compare affected, unaffected, outside and dehumidifier-exhaust GPP every day.
How GPP is calculated
From temperature and relative humidity: saturation vapor pressure at the temperature (ASHRAE Hyland-Wexler equation) × RH = vapor pressure e; humidity ratio W = 0.621945 × e ÷ (p − e) with p the barometric pressure for the elevation; GPP = W × 7,000. Dew point follows from the same vapor pressure.
What to compare
- Affected vs. unaffected: drying is progressing when affected GPP comes down toward the unaffected area.
- Dehumidifier exhaust vs. affected: the difference (grain depression) shows how much water each unit removes.
- Outside vs. inside: tells you whether opening the building would help or hurt.
Record it the same way every day
Same locations, same instrument, roughly the same time of day. One reading set per day and chamber is the backbone of the drying log.
GPP table (sea level)
| °F \ % RH | 20 % | 30 % | 40 % | 50 % | 60 % | 70 % | 80 % | 90 % |
|---|---|---|---|---|---|---|---|---|
| 60 °F | 15 | 23 | 31 | 38 | 46 | 54 | 62 | 69 |
| 65 °F | 18 | 27 | 37 | 46 | 55 | 64 | 74 | 83 |
| 70 °F | 22 | 33 | 43 | 54 | 66 | 77 | 88 | 99 |
| 75 °F | 26 | 39 | 52 | 65 | 78 | 91 | 104 | 118 |
| 80 °F | 30 | 46 | 61 | 76 | 92 | 108 | 124 | 140 |
| 85 °F | 36 | 54 | 72 | 90 | 109 | 127 | 146 | 165 |
| 90 °F | 42 | 63 | 84 | 106 | 128 | 150 | 172 | 195 |
| 95 °F | 49 | 74 | 99 | 124 | 150 | 176 | 202 | 229 |
| 100 °F | 57 | 86 | 116 | 145 | 176 | 206 | 238 | 269 |
Grains of water vapor per pound of dry air at 14.696 psia, calculated with the ASHRAE saturation-pressure equation. At higher elevations the same temperature and RH give slightly more grains.
Section numbers differ between editions of ANSI/IICRC S500, so this guide names the topic. Your copy of the current edition and your own professional judgment are the reference. This guide is general information, not legal advice. IICRC is a registered trademark of the Institute of Inspection, Cleaning and Restoration Certification. ANSI/IICRC S500 is the IICRC Standard for Professional Water Damage Restoration. Drypol is not affiliated with or endorsed by the IICRC; we cite the standard by topic and do not reproduce it.
Sources
- ASHRAE Handbook – Fundamentals, Chapter 1 Psychrometrics (saturation pressure, humidity ratio)
- IICRC – ANSI/IICRC S500 Standard for Professional Water Damage Restoration (purchase from the IICRC)
Let us document it for every job
Drypol Unlimited: equipment calculation, drying log, justification and scope – $1,000 a month, unlimited, 3 test cases free.
Related
- Drying Log Service
- IICRC S500 Drying Report
- Water Damage Categories 1, 2 and 3 Explained
- Classes of Water Damage
- How Many Air Movers per Room? Air Mover Calculation
- Dehumidifier Calculation
- Drying Goal and Dry Standard
- How to Justify Equipment Days on a Mitigation Job
- Flood Cuts and Removal Decisions in Water Mitigation
- Daily Moisture Log