Dehumidifier calculation: volume, class, rating
Pints per day needed = affected volume (cu ft) ÷ chart factor for the class and dehumidifier type. Number of units = pints per day ÷ the rated capacity of your unit, rounded up. Commonly used factors: LGR 100 / 50 / 40 / 50 for Class 1 / 2 / 3 / 4; conventional refrigerant 100 / 40 / 30 (Class 4 not recommended).
The calculation
- Affected volume = floor area × ceiling height of the drying chamber.
- Divide by the chart factor for the class and dehumidifier type (table above in the short answer).
- Divide the result by the rated pints per day of the unit you place, and round up.
Sample job: 4,288 cu ft ÷ 50 (Class 2, LGR) = 86 pints per day ÷ 70 pints per unit = 2 LGR dehumidifiers.
Which rating?
Manufacturers publish capacities at different test conditions. The DOE test procedure for consumer dehumidifiers moved to 65 °F; many commercial LGR units still list an “AHAM” rating at 80 °F / 60 % RH and a saturation rating. Use the rating basis that matches the chart factor you apply and state it in the calculation.
Desiccants and Class 4
Desiccant dehumidifiers are sized by airflow (air changes per hour), not by pints. Class 4 losses often need specialty drying. In both cases the reviewer sizes the system and documents it.
Check performance daily
The grain depression across each dehumidifier shows whether it is still removing water. A falling depression with readings still above goal is a reason to adjust, not to remove equipment.
Section numbers differ between editions of ANSI/IICRC S500, so this guide names the topic. Your copy of the current edition and your own professional judgment are the reference. This guide is general information, not legal advice. IICRC is a registered trademark of the Institute of Inspection, Cleaning and Restoration Certification. ANSI/IICRC S500 is the IICRC Standard for Professional Water Damage Restoration. Drypol is not affiliated with or endorsed by the IICRC; we cite the standard by topic and do not reproduce it.
Sources
- IICRC – ANSI/IICRC S500 Standard for Professional Water Damage Restoration (purchase from the IICRC)
- U.S. Department of Energy – Dehumidifier test procedure, 10 CFR 430 Subpart B, Appendix X1
Let us document it for every job
Drypol Unlimited: equipment calculation, drying log, justification and scope – $1,000 a month, unlimited, 3 test cases free.
Related
- Drying Equipment Calculation
- Water Mitigation Estimate Service
- Water Damage Categories 1, 2 and 3 Explained
- Classes of Water Damage
- How Many Air Movers per Room? Air Mover Calculation
- Grains per Pound
- Drying Goal and Dry Standard
- How to Justify Equipment Days on a Mitigation Job
- Flood Cuts and Removal Decisions in Water Mitigation
- Daily Moisture Log